Key facts
| Item | Value | Source |
|---|---|---|
| Voltage THD limit, PCC ≤ 1 kV | THD 8%, individual harmonic 5% | IEEE 519-2022 Table 1 (reproduced in ABB Technical Note 158)Checked: |
| Voltage THD limit, 1 kV < V ≤ 69 kV | THD 5%, individual harmonic 3% | IEEE 519-2022 Table 1 (reproduced in ABB Technical Note 158)Checked: |
| Voltage THD limit, above 69 kV | 69–161 kV: THD 2.5% (individual 1.5%); above 161 kV: THD 1.5% (individual 1%) | IEEE 519-2022 Table 1 (reproduced in ABB Technical Note 158)Checked: |
| THD definition (IEEE 519-2022) | RMS of harmonic content up to the 50th order as a percentage of the fundamental; interharmonics excluded | IEEE 519-2022 clause 3.1 definition (quoted in ABB Technical Note 158)Checked: |
| Power quality measurement method standard | IEC 61000-4-30:2015; Class A and Class S methods, including voltage harmonics | IEC 61000-4-30:2015, IEC WebstoreChecked: |
| Technical quality limits on Türkiye's distribution grid | Limit values are left to procedures and principles set by the EPDK Board | Regulation on Quality in Electricity Distribution and Retail Sales Activities (Kalite Yönetmeliği), Art. 25(2)Checked: |
What is total harmonic distortion (THD), and how is it calculated?
Total harmonic distortion (THD) is the ratio that expresses, as a number, how far the voltage or current waveform in an electrical network deviates from an ideal sine wave. In an ideal AC network, voltage and current are pure sine waves at the fundamental frequency (50 Hz in Türkiye and Europe, 60 Hz in North America). Nonlinear loads, however, add extra frequency components at exact multiples of the fundamental frequency, known as harmonics. THD gives the combined magnitude of these harmonic components relative to the fundamental, as a percentage.
Mathematically, THD is the square root of the sum of the squared RMS values of the harmonic components (2nd, 3rd, 5th, 7th and higher orders), divided by the RMS value of the fundamental (1st order) component. In practice, measuring instruments calculate this ratio by taking harmonics up to the 50th order into account. A THD of 0% indicates a pure sine wave; rising values point to an increasingly distorted waveform with notched peaks and troughs.
In short, THD is one of the most fundamental indicators of power quality. Low THD means a clean network in which transformers, motors, capacitors and sensitive electronics run safely, efficiently and with a long service life. High THD signals problems such as overheating, efficiency losses, nuisance tripping of protection relays and shortened equipment life.
What Is the Difference Between THD-V and THD-I?
THD-V measures distortion of the voltage waveform, while THD-I measures distortion of the current drawn by a specific load, and confusing the two is a common mistake. THD-V (voltage total harmonic distortion) is the distortion ratio of the supply voltage and is a direct measure of network cleanliness affecting every consumer at that point. THD-I (current total harmonic distortion) is the distortion ratio of the current a given load or facility draws from the network, and it shows how much that load contributes to distortion.
The distinction matters because a load can produce very high THD-I (for example, a variable frequency drive running at light load) while THD-V stays relatively low if the network impedance is low. Conversely, on a weak network even moderate harmonic currents can push voltage distortion above the limits. That is why current distortion is measured order by order at individual loads, while voltage distortion is evaluated for the network as a whole.
To assess current distortion more fairly, engineers use total demand distortion (TDD). TDD relates harmonic currents to the facility's maximum demand current rather than the instantaneous current. This prevents THD-I values that look high during light-load operation from overstating the facility's real impact. For this reason, IEEE 519 defines its current limits in terms of TDD.
What Causes Harmonics and What Are Their Effects?
Harmonics are caused mainly by nonlinear loads, meaning devices that draw a current that is not proportional to the applied voltage and is therefore not sinusoidal. In industrial facilities the most common sources are variable speed drives (VSDs/VFDs), rectifiers and UPS systems, arc furnaces and welding machines, LED drivers and fluorescent ballasts, and switch-mode power supplies. These loads typically generate 5th, 7th, 11th and 13th order harmonics.
The effects of high THD are not just theoretical; they show up directly in operating costs. Harmonic currents cause additional heating and losses in transformers and conductors, third-order harmonics accumulate in the neutral conductor and overload it, power factor correction capacitors can be driven into resonance and fail violently, and protection relays and meters can measure incorrectly.
Taken together, these effects shorten equipment life, increase unplanned downtime and reduce energy efficiency. Failing to consider harmonics together with reactive power compensation systems is the most common cause of unexpected capacitor failures, which is why facilities with harmonics use detuned compensation. When harmonics disrupt compensation, reactive charges can return as well; we cover how harmonics affect the reactive power penalty separately. Harmonic analysis should therefore be an integral part of every reactive power compensation design.
How Is Harmonic Distortion Measured?
Harmonic distortion is measured with a power quality analyzer. These instruments record voltage and current waveforms at a high sampling rate and use the FFT (Fast Fourier Transform) algorithm to break the signal down into its fundamental component and individual harmonic orders. The results are reported as a percentage for each order and as an overall THD value.
The method for reliable, standards-compliant measurement is well defined. IEC 61000-4-7 specifies the measurement technique and windowing method for harmonic measurement (a 10-cycle window of about 200 ms on a 50 Hz network). IEC 61000-4-30 defines how power quality parameters are measured and classified (Class A/S). For a meaningful assessment, measurement should typically run for at least one week and cover every load condition of the facility, including production, shift changes and idle periods.
A single spot reading can be misleading, because harmonic levels vary considerably throughout the day depending on the load profile. An accurate diagnosis requires choosing the right measurement points (main switchboard, sub-distribution panels, problem load feeders), monitoring current and voltage distortion simultaneously and evaluating the data as trends. As part of our power quality analysis service, Miratek carries out on-site measurements in line with these standards, maps the harmonic spectrum order by order and reports the results together with recommended solutions.
What Are the THD Limits Under IEEE 519 and IEC 61000?
The two most widely used international frameworks for harmonic limits are IEEE 519 and the IEC 61000 series. IEEE 519-2022 defines its limits at the point of common coupling (PCC): voltage THD is limited to 8% at or below 1 kV (5% for any individual harmonic), 5% between 1 kV and 69 kV (individual 3%), 2.5% between 69 kV and 161 kV (individual 1.5%) and 1.5% above 161 kV (individual 1%). THD is calculated using harmonics up to the 50th order. The standard states explicitly that these limits apply at the PCC between the system operator and the user, not to the evaluation of individual equipment.
On the current side, IEEE 519 does not use a single THD-I figure; instead it defines TDD limits that vary with the facility's short-circuit ratio to the network (Isc/IL). Consumers that are 'small' relative to the network are allowed more distortion and 'large' consumers less, so each consumer's contribution to the quality of the shared network is limited fairly.
The IEC side has a multi-layered structure. IEC 61000-2-2 and IEC 61000-2-4 set compatibility levels, meaning the acceptable distortion levels for low-voltage public networks and industrial installations. IEC 61000-3-2 and IEC 61000-3-12 define the harmonic current emission limits that equipment may inject into the network. On the measurement side, IEC 61000-4-30:2015 defines how power quality parameters, including voltage harmonics, are measured using Class A and Class S methods.
Where are harmonic limits set in Türkiye? Technical quality on the distribution grid is governed by the Regulation on Quality in Electricity Distribution and Retail Sales Activities, in force since 1 January 2021, which repealed the 2012 Service Quality Regulation (Art. 48). Article 25 defines technical quality in terms of the frequency, magnitude, waveform and three-phase symmetry of the voltage, and leaves technical quality parameters and limit values to procedures and principles set by the EPDK Board (Art. 25(2)). The limit that applies at your connection point should therefore be confirmed with your distribution company and EPDK's current rules.
How Can High THD Be Reduced?
High THD is reduced by choosing a mitigation method that matches the harmonic source and order profile identified through measurement; there is no one-size-fits-all solution. Passive harmonic filters are reactor and capacitor combinations tuned to a specific order, such as the dominant 5th harmonic; they are economical and robust, and suit facilities with a stable, dominant harmonic profile. Adding reactors (line or DC chokes) at drive inputs is also a simple, cost-effective first step to reduce current distortion.
Active harmonic filters inject harmonic currents in antiphase into the network in real time and dynamically suppress a wide range of orders. They are the most flexible solution for facilities with variable load profiles and many different harmonic sources. Multi-pulse (12- or 18-pulse) rectifier configurations and harmonic-rated (K-factor) transformers are preventive options that can be specified at the design stage. We compare the two filter types in active or passive harmonic filter.
The right solution is determined by evaluating measurement data, the harmonic spectrum, compensation needs and resonance risk together; where network-wide resonance and filter effects need to be studied, a power system analysis is carried out. Miratek Elektrik runs an integrated engineering process within its power quality service, from on-site measurement and filter design to panel manufacturing and commissioning. Our harmonic filter panels and reactive power compensation panels are among the 340+ panels of all types we have manufactured to date; at Toreks, for example, harmonic effects were assessed with reference to the IEC 61000 family alongside the manufacture of a compensation panel. By addressing harmonic mitigation and reactive power compensation together, we aim to bring THD below standard limits and minimize the risk of reactive power penalties.
Frequently Asked Questions
What does THD mean in simple terms?+
THD (total harmonic distortion) is the degree to which a network's voltage or current waveform deviates from an ideal sine wave. It is expressed as a percentage: 0% indicates a pure sine wave, while higher values indicate a distorted waveform that puts equipment at risk.
What should the THD limit be?+
Under IEEE 519-2022, voltage THD at the point of common coupling should not exceed 8% on systems at or below 1 kV (5% for any individual harmonic) and 5% on 1-69 kV systems (3% for any individual harmonic); limits tighten at higher voltages. Current distortion is assessed with TDD limits that depend on the short-circuit ratio to the network. In Türkiye, technical quality limits for the distribution grid are left to procedures and principles set by the EPDK Board under Article 25(2) of the Quality Regulation.
What is the difference between THD-V and THD-I?+
THD-V measures distortion of the voltage waveform and reflects the network quality that affects every consumer at that point. THD-I measures distortion of the current drawn by a load and shows how much that load contributes to distortion.
How is harmonic distortion measured?+
With a power quality analyzer that uses FFT to break the waveform down into harmonic orders. For reliable results, a measurement of at least one week that complies with IEC 61000-4-7 and IEC 61000-4-30 and covers all load conditions is recommended.
What problems does high THD cause?+
High THD causes overheating in transformers and cables, neutral conductor overloading, resonance and failure of compensation capacitors, nuisance tripping of protection relays and shortened equipment life.
How can THD be reduced?+
Passive filters and reactors are used for dominant, stable harmonics, and active harmonic filters for variable load profiles. At the design stage, multi-pulse rectifiers and K-factor transformers also help prevent harmonic generation.
Sources
- IEEE 519-2022 IEEE Standard for Harmonic Control in Electric Power Systems — IEEE Standards Association, (accessed: 2026-10-05)
- ABB Technical Note 158: IEEE 519-2022 Review (secondary source reproducing the standard's table) — ABB, (accessed: 2026-10-05)
- IEC 61000-4-30:2015 Power quality measurement methods — IEC, (accessed: 2026-10-05)
- Regulation on Quality in Electricity Distribution and Retail Sales Activities (Kalite Yönetmeliği) — mevzuat.gov.tr (EPDK), (accessed: 2026-10-05)
Related
